EAGLE 120® WIRELESS POWER QUALITY ANALYZER | ||
| INPUTS | AC Voltage | 60 to 140 VAC RMS Continuous, 0 to 240 VAC Peak, Neutral-Ground |
| AC Current | 0 to 80 amps RMS (15 amps continuous) | |
| Sample Rate | 256 samples/cycle/channel | |
| CHANNELS | Voltage | 2 channels |
| Current | 1 channel | |
| MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps | |
| Real Power | Watts | |
| Apparent Power | VAs | |
| Reactive Power | VARs | |
| Phase Angle | Degrees | |
| Power Factor | Watts/VA | |
| Displacement PF | cos (phase angle) | |
| Power Usage | kWh, kVARh, kVAh | |
| COMMUNICATIONS | Type | USB, Bluetooth® Wireless (optional) |
| INFORMATION STORAGE | Interval Graphs | 1.2 MB (Standard) 6.9 MB (with memory option) |
| Significant Change | 1000 records | |
| Flicker | 1000 records | |
| Waveform Capture | 256 KB (standard) 1.7 MB (with memory option) | |
| RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes |
| Significant Change | 1V to 8V in 1V steps | |
| Flicker | User-defined, or conform to IEEE1453/IEC61000-4-15,and IEEE Std. 141 | |
| Waveform Capture | Voltage and current threshold, periodic capture | |
| ENVIRONMENTAL | Operating Temp | - 20°F to + 135° F |
| Shock | 60 Hz to 2 KHz, acceleration 25G | |
| Vibration | 10Hz to 60Hz, amplitude 1.8mm | |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale | |
| Power | 1.0% of full scale | |
| Phase Angle | 1.0° | |
| Power Factor | ±0.02 | |
| Displacement PF | ±0.02 | |
| PHYSICAL DIMENSIONS | Size | 4.9” L x 2.7” W x 1.25” H |
| Weight | 0.5 lbs | |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st | |
| Measures | magnitude, phase, THD | |