ULTRA SLIM FLEXIBLE CURRENT PROBES (FLEX CTs) | ||
| ELECTRICAL SPECIFICATIONS | Switchable Ranges | 1 to 100A, 1 to 1000A, 1 to 5000A |
| Operating Limit | 1 to 5000A | |
| Controls | Range is chosen from the recorder, PC, or PDA software. | |
| Power Source | Power is supplied by connection to PMI recorder. No external battery or other power source is required. | |
| Linearity | ±0.05% | |
| Phase Shift | ≤ ±0.5% at 50 to 60 Hz | |
| Frequency Range | 8Hz to 10kHz | |
| Crest Factor (mid range) | 100A and 1000A scale: 3.0 5000A scale: 1.6 | |
| Position Sensitivity | ±1.5% 1 in from connector | |
| PMI RECORDER CAPABILITY | iVS-3/600E may require firmware upgrade. | |
| MECHANICAL MATERIALS | Sensor Jacket | Polyurethane UL94V0 |
| Connector | FR Polypropylene UL94V0 | |
| Cable Jacket | Polyurethane UL94V0 | |
| ENVIRONMENTAL | Operating Temperature | -20 to 135° F (-29 to57° C) |
| Altitude Operating | 0 to 2000m, derated above 2000m | |
| Case Protection | Sensor and Module IP65 per IEC 529 | |
| PHYSICAL DIMENSIONS | Min. Bending Radius | 1 in (25.4 mm) |
| Sensor Diameter | .310 in (7.9 mm) | |
| Connector Diameter | 1.07 in max (27.2 mm) | |
| Sensor Output Cable Length | 48 in (1.2 m) | |
| ACCURACY | ± 1% of full scale | |
| WORKING VOLTAGE | Sensor | 600V AC to earth |
| Module | 600V AC to earth | |
| SAFETY | Double Insulated | |
| Sensor | 600V CAT IV | |
| Module | 600V CAT III | |
| Pollution Degree 2 | ||