20/200A TRUE LOW AMP RANGE AC CURRENT PROBES | |||
| ELECTRICAL SPECIFICATIONS | Current Ranges | 20A, 200A AC | 20A, 200A AC |
| Operating Limit | 200A Continuous | 200A Continuous | |
| Frequency Range | 40 to 10kHz | 40 to 10kHz | |
| Working Voltage | 600 VAC max | 600 VAC max | |
| Influence of conductor position in jaw | 0.5% of reading at 50/60Hz | 0.5% of reading at 50/60Hz | |
| Influence of adjacent conductor | 1.50% | 1.50% | |
| Influence of frequency | 40Hz to 1kHz: 3% of reading, 1kHz to 10kHz: 12% of reading | 40Hz to 1kHz: 3% of reading,1kHz to 10kHz: 12% of reading | |
| PHASE SHIFT | 1-20A | ≤ 3 degrees | ≤ 3 degrees |
| 20-80A | ≤ 2 degrees | ≤ 2 degrees | |
| 80-200A | ≤2.5 degrees | ≤2.5 degrees | |
| ACCURACY | 20A scale | 1 to 20 A: 1.5% of reading ±0.1A | 1 to 20 A: 1.5% of reading ±0.1A |
| 200A scale | 1.5% of reading ±0.5A | 1.5% of reading ±0.5A | |
| SAFETY | Rating | UL 61010B-1 | |
| IEC 61010-1 | IEC 61010-1 | ||
| 600V CAT III | 600V CAT III | ||
| PMI RECORDER CAPABILITY | 10A range only with iVS-3/600E and ViPs with SNs lower than 61000, otherwise adjustable 20A/200A range | ||
| ENVIRONMENTAL | Operating Temp | 14 to 131° F -10 to 55° C | 14 to 131° F -10 to 55° C |
| Operating Relative Humidity | 10-35° C 85% RH | 10-35° C 85% RH | |
| Case Protection | Probes - IP40, Enclosure - IP65 | Probes - IP40, Enclosure - IP65 | |
| PHYSICAL DIMENSIONS | Maximum Conductor Size | 0.78 in (20 mm), bus bar20 x 5 mm | 0.59 in (15 mm) |
| Probes | 5.47 x 2.00 x 1.18 in (139 x 51 x 30 mm) | 5 x 1.67 x 0.93 in bus bar15 x 17 mm | |
| Enclosure | 2.36 x 1.38 x 0.67 in | 2.36 x 1.38 x 0.67 in | |
| Weight | TLAR+200/3 - 0.75 lb TLAR+200/4 - 1.00 lb | TLAR+200/3 - 0.75 lb TLAR+200/4 - 1.00 lb | |
| Probe Leads | 4 ft, 600V rating | 4 ft, 600V rating | |
| Output Cable | 9 in, 600V rating | 9 in, 600V rating | |