| GUARDIAN |
| INPUTS | AC Voltage | 0 to 150 VAC per channel |
| AC Current | 200 Amps RMS |
| Sample Rate | 256 samples/cycle/channel |
| CHANNELS | Voltage | 2 channels |
| Current | 2 channels |
MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps |
| Real Power | Watts |
| Apparent Power | VAs |
| Reactive Power | VARs |
| Phase Angle | Degrees |
| Power Factor | Watts/VA |
| Displacement PF | cos (phase angle) |
| Power Usage | kWh, kVARh, kVAh |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale |
| Power | 1.0% of full scale |
| Phase Angle | 1.0° |
| Power Factor | ±0.02 |
| Displacement PF | ±0.02 |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st |
| Measures | magnitude, phase, THD |
| COMMUNICATIONS | Type | Bluetooth®Wireless, USB |
| Remote | Cell modem option |
| Data Rate | |
| INFORMATION STORAGE | Interval Graphs | 6.9 MB |
| Significant Change | 1000 records |
| Flicker | 1000 records |
| Waveform Capture | 1.7 MB |
RECORD SETTINGS | Interval Graphs | 1 second to 4 hour interval user selected, stop-when-full, or wrap around memory modes |
| Significant Change | 1V to 8V in 1V steps |
| Flicker Settings | User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141. |
| Waveform Capture | Voltage and current threshold, periodic capture |
| POWER SUPPLY | Power Consumption | Less than 2.5 watts |
| Operating Temp | -20°F to +135°F |
| Shock | 60 Hz to 2kHz, Acceleration 25G |
| PHYSICAL DIMENSION | Vibration | 10 Hz to 60 Hz, Amplitude 1.8 mm |
| Size | 4.625” x 6.75” |
| Weight | 3.6 lbs |
| POWER FAIL OPERATION | Can operate without any input voltage for up to 30 minutes. This allows it to record down to 0 volts on all channels during power outages. |
| EAGLE® 120 |
|
| INPUTS | AC Voltage | 60 to 140 VAC, 0 to 240 VAC Peak, Neutral-Ground 0-75 VAC RMS |
| AC Current | 0 to 80 Amps RMS (15 Amps continuous) |
| Sample Rate | 256 samples/cycle/channel |
| CHANNELS | Voltage | 2 channels |
| Current | 1 channel |
MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps |
| Real Power | Watts |
| Apparent Power | VAs |
| Reactive Power | VARs |
| Phase Angle | Degrees |
| Power Factor | Watts/VA |
| Displacement PF | cos (phase angle) |
| Power Usage | kWh, kVARh, kVAh |
| COMMUNICATIONS | Type | USB, Bluetooth®Wireless (optional) |
INFORMATION STORAGE | Interval Graphs | 1.2 MB (Standard) 6.9 MB (with memory option) |
| Significant Change | 1000 records |
| Flicker | 1000 records |
| Waveform Capture | 256 KB (standard) 1.7 MB (with memory option) |
RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes |
| Significant Change | 1V to 8V in 1V steps |
| Flicker | User-defined, or conform to IEEE1453/IEC61000-4-15,and IEEE Std. 141 |
| Waveform Capture | Voltage and current threshold, periodic capture |
| ENVIRONMENTAL | Operating Temp | -20°F to +135°F |
| Shock | 60 Hz to 2 kHz, acceleration 25G |
| Vibration | 10Hz to 60Hz, amplitude 1.8mm |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale |
| Power | 1.0% of full scale |
| Phase Angle | 1.0° |
| Power Factor | ±0.02 |
| Displacement PF | ±0.02 |
PHYSICAL DIMENSIONS | Size | 4.9” L x 2.7” W x 1.25” H |
| Weight | 0.5 lbs |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st |
| Measures | magnitude, phase, THD |