| Inputs |
| AC Voltage |
0 to 600 V RMS continuous per phase (5 kV peak transients) |
| AC Current |
0 to 5000 amps |
| Sample Rate |
Up to 1 MHz voltage (16666 samples/cycle), |
| 250 kHz current (4166 samples/cycle) |
| Channels |
| Voltage |
4 channels |
| Current |
4 channels |
| Accuracy |
| Voltage |
0.33% of full scale w/o probe |
| Current |
1.0% of full scale w/o probe |
| Power |
1.0% of full scale w/o probe |
| Phase Angle |
1.0% of full scale w/o probe |
| Power Factor |
±0.02% of full scale w/o probe |
| Displacement PF |
±0.02% of full scale w/o probe |
| Harmonics |
| Voltage |
to the 51st |
| Current |
to the 51st |
| Communications |
| Type, Standards |
Bluetooth® |
| Wireless, USB |
| Remote Options |
Ethernet, Cell Modem, Wi-Fi |
| Information Storage |
| Memory |
| 16 MB (Standard) |
| 128 MB (Optional) |
| 512 MB (Optional) |
| 1 GB (Optional) |
| Record Settings |
| Interval Graphs |
User-defined |
| Significant Change |
User-defined |
| Flicker Settings |
User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141 |
| Environmental |
| Operating Temp |
-20° F to + 135° F |
| Humidity |
Less than or equal to 85% |
| Shock |
60 Hz to 2 KHz, acceleration 25G |
| Vibration |
10 Hz to 60 Hz, amplitude 1.8mm |
| Max Altitude |
2.0 km (6560 ft) |
| Physical Dimensions |
| Size |
5.15"L x 3.45"W x 1.85"H |
| Weight |
less than 1 lb |
| Case |
NEMA 4X |
| Power Fail Operation |
| The recorder can operate without any input voltage for up to 2 hours. This allows it to record down to 0 volts on all channels during power outages. |