The Vision® Kit contains everything that you need to instantly access power quality data while reducing the risk of injury due to arc flash.

The Vision power analyzer is the most reliable and portable choice when it comes to simultaneously retrieving and analyzing power quality data. Our engineers have simplified things considerably by providing complete functionality by way of a user-friendly interface with soft-key controls.
Weighing in at just 16 ounces, the handheld Vision continues to be the smallest transient power analyzer in the world. Use it to view real-time waveforms, make spot measurements, take measurement snapshots, or leave it in place for power logging in a controlled environment. The Vision measures voltage, current, power quantities, harmonics, and flicker. Includes: VisionPro Flex 4/24 (set of four twenty-four inch Flex CTs) TLAR 4 (set of four 20/200A TLARs) Loaded Eagle 120 receptacle power quality analyzer Large high-impact plastic foam-lined carrying case.

Kit Contents

  • Vision Pro Handheld PQ Analyzer

  • FCT 4/12 Ultra Slim Four channel 100/1000/5000A flexible 12 in. CTs

  • FCT 4/24 Ultra Slim Four channel 100/1000/5000A flexible 24 in. CTs

  • TLAR 4 Four channel 20/200A iron-core CTs

  • Eagle 120 with Bluetooth and 8MB memory

  • Large Hard Carrying Case

VISIONPRO®
INPUTSAC Voltage0 to 600 RMS continuous per channel (±5 kV peak transients)
AC Current0 to 5000 Amps
Sample Rate1 MHz Voltage (16666 samples/cycle), 250 kHz current (4166 samples/cycle)
CHANNELSVoltage4 channels
Current4 channels
MEASURED
QUANTITIES
PER CYCLE
RMS VoltageVolts
RMS CurrentAmps
Real PowerWatts
Apparent PowerVAs
Reactive PowerVARs
Phase AngleDegrees
Power FactorWatts/VA
Displacement PFcos (phase angle)
Power UsagekWh, kVARh, kVAh
ACCURACYVoltage0.33% of full scale
Current1.0% of full scale w/o probe
Power1.0% of full scale w/o probe
Phase Angle1.0° w/o probe
Power Factor±0.02 w/o probe
Displacement PF±0.02 w/o probe
SAFETYRatingIEC 61010-1, 600V CAT IV
HARMONICSVoltageto the 51st
Currentto the 51st
Measuresmagnitude, phase, THD
COMMUNICATIONSType StandardBluetooth®2.0 Class 1 Wireless, USB 2.0, 10/100MB Ethernet
INFORMATION STORAGE Data Storage1 GB
Significant Change1000 records
Flicker 1000 records
RECORD SETTINGSInterval Graphs1 cycle/second to 4 hour interval. User selected, stop-when-full, or wrap around memory modes
Significant Change1V to 8V in 1V steps
Flicker SettingsUser-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141
Waveform CaptureVoltage and current threshold, periodic capture, waveshapes, event cross triggers
Transient CapturePeak voltage threshold
POWER SUPPLY Requirements Internal battery, USB charger
ENVIRONMENTALIP51 rating
PHYSICAL DIMENSIONSSize7” L X 4.5” W X 1.4” H
Weight1.2 lbs
BATTERY10 hour run-time
EAGLE 120
INPUTSAC Voltage60 to 140 VAC, 0 to 240 VAC Peak, Neutral-Ground 0-75 VAC RMS
AC Current0 to 80 Amps RMS (15 Amps continuous)
Sample Rate256 samples/cycle/channel
CHANNELSVoltage2 channels
Current1 channel
MEASURED
QUANTITIES
PER CYCLE
RMS VoltageVolts
RMS CurrentAmps
Real PowerWatts
Apparent PowerVAs
Reactive PowerVARs
Phase AngleDegrees
Power FactorWatts/VA
Displacement PFcos (phase angle)
Power UsagekWh, kVARh, kVAh
COMMUNICATIONSTypeUSB, Bluetooth®Wireless (optional)
INFORMATION
STORAGE
Interval Graphs1.2 MB (Standard) 6.9 MB (with memory option)
Significant Change1000 records
Flicker 1000 records
Waveform Capture256 KB (standard) 1.7 MB (with memory option)
RECORD
SETTINGS
Interval Graphs1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes
Significant Change1V to 8V in 1V steps
Flicker User-defined, or conform to IEEE1453/IEC61000-4-15,and IEEE Std. 141
Waveform CaptureVoltage and current threshold, periodic capture
ENVIRONMENTALOperating Temp-20°F to +135°F
Shock60 Hz to 2 kHz, acceleration 25G
Vibration10Hz to 60Hz, amplitude 1.8mm
ACCURACYVoltage0.33% of full scale
Current1.0% of full scale
Power1.0% of full scale
Phase Angle1.0°
Power Factor±0.02
Displacement PF±0.02
PHYSICAL
DIMENSIONS
Size4.9” L x 2.7” W x 1.25” H
Weight0.5 lbs
HARMONICSVoltageto the 51st
Currentto the 51st
Measuresmagnitude, phase, THD
ULTRA SLIM FLEX CTs
ELECTRICAL SPECIFICATIONS Switchable Ranges 1 to 100A, 1 to 1000A, 1 to 5000A
Operating Limit 1 to 5000A
Controls Range is chosen from the recorder, PC, or PDA software.
Power Source Power is supplied by connection to PMI recorder. No external battery or other power source is required.
Linearity ±0.05%
Phase Shift ≤±0.5% at 50 to 60 Hz
Frequency Range 8Hz to 10kHz
Crest Factor (mid range) 100A and 1000A scale: 3.0 5000A scale: 1.6
Position Sensitivity ±1.5% 1 in from connector
WORKING VOLTAGE Sensor 600V AC to earth
Module 600V AC to earth
ACCURACY ± 1% of full scale
SAFETY Double Insulated
Sensor 600V CAT IV
Module 600V CAT III
Pollution Degree 2
PMI RECORDER CAPABILITY iVS-3/600E may require a firmware upgrade
ELECTRICAL SPECIFICATIONS Switchable Ranges 1 to 100A, 1 to 1000A, 1 to 5000A
Operating Limit 1 to 5000A
Controls Range is chosen from the recorder, PC, or PDA software.
Power Source Power is supplied by connection to PMI recorder. No external battery or other power source is required.
Linearity ±0.05%
Phase Shift ≤±0.5% at 50 to 60 Hz
Frequency Range 8Hz to 10kHz
Crest Factor (mid range) 100A and 1000A scale: 3.0 5000A scale: 1.6
Position Sensitivity ±1.5% 1 in from connector
WORKING VOLTAGE Sensor 600V AC to earth
Module 600V AC to earth
ACCURACY ± 1% of full scale
SAFETY Double Insulated
Sensor 600V CAT IV
Module 600V CAT III
Pollution Degree 2
PMI RECORDER CAPABILITY iVS-3/600E may require a firmware upgrade
MECHANICAL MATERIALS Sensor Jacket Polyurethane UL94V0
Connector FR Polypropylene UL94V0
Cable Jacket Polyurethane UL94V0
PHYSICAL DIMENSIONS Min. Bending Radius 1 in (25.4 mm)
Sensor Diameter .310 in (7.9 mm)
Connector Diameter 1.07 in max (27.2 mm)
Sensor Output Cable Length 48 in (1.2 m)
ENVIRONMENTAL Operating Temperature -20 to 135°F (-29 to 57°C)
Altitude Operating 0 to 2000m, derated above 2000m
Case Protection Sensor and Module IP65 per IEC 529
PMI CT MODEL NUMBER .../12 .../24 .../36 .../48
LENGTH (OPEN) 12 in.
305 mm
24 in.
610 mm
36 in.
915 mm
48 in.
1220 mm
O.D. (CLOSED) 4.15 in.
105 mm
8.3 in.
210 mm
12 in.
305 mm
15.9 in.
404 mm
I.D. (CLOSED) 3.5 in.
89 mm
7 in.
178 mm
10.9 in.
277 mm
14.7 in.
372 mm
 
TLAR
ELECTRICAL SPECIFICATIONSCurrent Ranges20A, 200A AC
Operating Limit200A Continuous
Frequency Range40 to 10kHz
Working Voltage600 VAC max
Influence of conductor position in jaw0.5% of reading at 50/60Hz
Influence of adjacent conductor1.50%
Influence of frequency40Hz to 1kHz: 3% of reading, 1kHz to 10kHz: 12% of reading
PHASE SHIFT1-20A≤3 degrees
20-80A≤2 degrees
80-200A≤2.5 degrees
ACCURACY20A scale1 to 20 A: 1.5% of reading ±0.1A
200A scale1.5% of reading ±0.5A
SAFETYRatingUL 61010B-1
IEC 61010-1
600V CAT III
PMI RECORDER
CAPABILITY
10A range only with iVS-3/600E and ViPs with SNs lower than 61000, otherwise adjustable 20A/200A range
ENVIRONMENTALOperating Temp14 to 131°F -10 to 55°C
Operating Relative Humidity10-35°C 85% RH
Case ProtectionProbes - IP40, Enclosure - IP65
PHYSICAL
DIMENSIONS
Maximum Conductor Size0.78 in (20 mm), bus bar 20 x 5 mm
Probes5.47 x 2.00 x 1.18 in (139 x 51 x 30 mm)
Enclosure2.36 x 1.38 x 0.67 in
WeightTLAR+200/3 - 0.75 lb TLAR+200/4 - 1.00 lb
Probe Leads4 ft, 600V rating
Output Cable9 in, 600V rating