| Base price | $420.00 |
| Features | |
| None | +0.00 |
| 8 MB | +210.00 |
| Bluetooth® | +265.00 |
Overview
Features:
- Lightweight (0.5 lbs.)
- Palm Sized (4.875" L x 2.625" W x 1.25" H)
- High-Impact ABS Plastic Case
- Fast, Single Cycle Response
- 1 MB memory, 8 MB Optional (battery backed)
Advanced Functionality:
- Monitor True RMS Voltage and Current
- IEEE 1453/IEC61000-4-15 Flicker
- Harmonics to the 51st degree
- Minimum/Maximum/Average Recording
- Real/Reactive/Apparent Power Recording
- Waveform capture
Description
The Eagle 120 has all the power of the Eagle 440 in a 120 volt receptacle. The Eagle 120 power analyzer is the easiest, most advanced diagnostic tool for detecting power quality issues originating from inside a commercial or residential building.
It’s a complete ten function plug-in receptacle power quality analyzer that monitors two channels voltage and one channel of current in single-phase applications.
When plugged into a standard 120V receptacle, it continuously detects and monitors sags, swells, flicker, RMS voltage, current, power factor, and harmonics. Additionally, the Eagle 120 captures waveforms from custom-triggered events. Real-time and monitored power quality measurements are downloaded via Bluetooth wireless communications link (optional) or USB cable.
- Fast, single cycle response
- Waveform capture
- High impact case and lightweight design
Specs
| INPUTS | AC Voltage | 60 to 140 VAC, 0 to 240 VAC Peak, Neutral-Ground 0-75 VAC RMS |
| AC Current | 0 to 80 Amps RMS (15 Amps continuous) | |
| Sample Rate | 256 samples/cycle/channel | |
| CHANNELS | Voltage | 2 channels |
| Current | 1 channel | |
| MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps | |
| Real Power | Watts | |
| Apparent Power | VAs | |
| Reactive Power | VARs | |
| Phase Angle | Degrees | |
| Power Factor | Watts/VA | |
| Displacement PF | cos (phase angle) | |
| Power Usage | kWh, kVARh, kVAh | |
| COMMUNICATIONS | Type | USB, Bluetooth®Wireless (optional) |
| INFORMATION STORAGE | Interval Graphs | 1.2 MB (Standard) 6.9 MB (with memory option) |
| Significant Change | 1000 records | |
| Flicker | 1000 records | |
| Waveform Capture | 256 KB (standard) 1.7 MB (with memory option) | |
| RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes |
| Significant Change | 1V to 8V in 1V steps | |
| Flicker | User-defined, or conform to IEEE1453/IEC61000-4-15,and IEEE Std. 141 | |
| Waveform Capture | Voltage and current threshold, periodic capture | |
| ENVIRONMENTAL | Operating Temp | -20°F to +135°F |
| Shock | 60 Hz to 2 kHz, acceleration 25G | |
| Vibration | 10Hz to 60Hz, amplitude 1.8mm | |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale | |
| Power | 1.0% of full scale | |
| Phase Angle | 1.0° | |
| Power Factor | ±0.02 | |
| Displacement PF | ±0.02 | |
| PHYSICAL DIMENSIONS | Size | 4.9” L x 2.7” W x 1.25” H |
| Weight | 0.5 lbs | |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st | |
| Measures | magnitude, phase, THD |