| Base price | $4,795.00 |
Overview
Multiple Configurations:
Three configurations of Eagle® wireless power quality monitors provide wireless monitoring solutions for substation, industrial, and commercial applications
- 220 Series features two sets of voltage and current inputs for light commercial applications.
- 330 Series features three sets of voltage and current inputs for single and three phase commercial and industrial applications.
- 440 Series features four sets of voltage and current inputs for advanced 1-, 2-, and 3-phase applications, as well as neutral-to-ground applications.
Communications:
Eagle® recorders can be quickly and easily identified, initialized, and downloaded remotely - even when they are installed in hard to reach, hazardous, and secure locations. They utilize Bluetooth® technology to communicate with selected Palm®-platform PDAs, and Bluetooth®-equipped laptops. USB communication is also available.
Real-time Harmonics and Waveforms:
Eagle® wireless power quality recorders calculate and display waveforms and harmonic values for triggered events on all monitored channels. Users may then display and download them in real-time via wireless or USB cable.
Description
The Eagle series of power analyzers are the smallest, lightest full function power quality analyzer currently available. Eagle Wireless power quality analyzers are the first digital power quality analyzers to wirelessly provide real-time power quality measurement.
They measure just 5 3/8"L x 2 3/8"W x 1 13/16"H, and weigh less than 1 lb. each. Don’t be fooled by their light weight and compact size - Eagle power analyzers outperform bigger, bulkier, and more expensive monitors in a wide range of portable power quality monitoring applications. These rugged, all-weather, wireless power analyzers go where other power analyzers cannot to wirelessly transmit critical power quality data measurements.
The Eagle 440 will still read data even if it is in a closed box or an enclosed area. Eagle power quality analyzers incorporate state-of-the-art Bluetooth technology to monitor power quality data and wirelessly transmit it to Bluetooth- equipped laptops, desktops. With an Eagle power quality analyzer, you can instantly access power quality data being monitored behind a locked security fence, in a transformer buried underground, or from restricted areas where distribution voltage would otherwise pose a safety hazard to crews.
The Eagle’s generous 8MB of memory also means you can store power quality data for up to two years, and then download it for detailed analysis as needed. You can also download the Eagle using a standard USB connection to your PC.
Specs
| INPUTS | AC Voltage | 0 to 600 VAC |
| AC Current | 0 to 5000 Amps with CT probes | |
| Sample Rate | 15,360 samples per second/channel; 256 samples per cycle | |
| CHANNELS | Voltage | 2, 3, or 4 channels |
| Current | 2, 3, or 4 channels | |
| MEASURED| QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps | |
| Real Power | Watts | |
| Apparent Power | VAs | |
| Reactive Power | VARs | |
| Phase Angle | Degrees | |
| Power Factor | Watts/VA | |
| Displacement PF | cos (phase angle) | |
| Power Usage | kWh, kVARh, kVAh | |
| ACCURACY | Voltage | ±0.33% of full scale |
| Current | ±1.0% of full scale w/o probe | |
| Power | ±1.0% of full scale w/o probe | |
| Phase Angle | ±1.0° w/o probe | |
| Power Factor | ±0.02 w/o probe | |
| Displacement PF | ±0.02 w/o probe | |
| SAFETY | Pollution Degree 2 | 600V CAT III |
| UL Listed | UL/IEC 61010 | |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st | |
| Measures | magnitude, phase, THD | |
| COMMUNICATIONS | Bluetooth®Wireless, USB | |
| INFORMATION STORAGE | Interval Graph | 6.9 MB |
| Significant Change | 1000 records | |
| Flicker | 1000 records | |
| Waveform Capture | 3.75 MB | |
| RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes |
| Significant Change | 1V to 8V in 1V steps | |
| Flicker | User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141 | |
| Waveform Capture | Voltage and current threshold, periodic capture | |
| POWER SUPPLY REQUIREMENTS: ENVIRONMENTAL | Voltage | 60-600VAC Channel 1 to Common (47-63Hz) |
| Power Consumption | 1.5 Watts max, 9VA max at 600VAC | |
| Operating Temp | -22°F to +131°F | |
| Humidity | Less than or equal to 85% | |
| Shock | 60 Hz to 2 kHz, acceleration 25G | |
| Vibration | 10 Hz to 60 Hz, amplitude 1.8mm | |
| Max Altitude | 2.0 km (6560 ft), derated above 2.0 km | |
| PHYSICAL DIMENSIONS | Size | 4.375”L x 3.375”W x 1.812”H |
| Weight | less than 1 lb | |
| Case | NEMA 4X | |
| POWER FAIL OPERATION | Specifications | These recorders can operate without any input voltage for up to 2 hours. This allows it to record down to 0 volts on all channels during power outages. |