Base price $5,295.00
Features
16 MB +0.00
128 MB +75.00
512 MB +125.00
1 GB +250.00
Ethernet +525.00
Cell Modem +695.00
Transient Capture +1575.00

Overview

Features:

  • CAT IV 600 volt rating
  • Up to 1 Megahertz voltage sampling
  • Up to 5kV transient capture
  • Up to 1 GB internal memory

Unrivaled Communication Options:

  • USB 2.0
  • Ethernet
  • Bluetooth® 2.0
  • Cell Modem

Description

Reduce fleet and labor costs with this small, rugged, lightweight power quality analyzer. The Revolution is PMI’s state of the art high speed transient power quality monitor with industry leading communications capabilities. The included ProVision software lets you monitor real-time current, flicker, voltage, power factor and more from your desktop, or use a laptop, the PMI Field PC, or a PDA to monitor data from the field.

Benefits:

  • 600V CAT IV: For use in a wide range of monitoring environments
  • Pocket-size: Can be installed inside meter bases, transformers, and panels
  • Bluetooth® 2.0, Cell Phone Modem (optional): Stay safe with wireless data behind closed panel covers
  • USB 2.0, built in Ethernet Networking (Optional): For permanent installations
  • High sampling rate: Captures high speed transients up to 5000V and 1 MHz.
  • UL listed: Increased user safety
  • Large memory capacity: Longer monitoring time and very high resolution wave capture.
  • NEW Features: E-mail & text alerts, network time sync.

Specs

INPUTSAC Voltage0 to 600 RMS continuous per phase
(±5 kV peak transients)
AC Current0 to 5000 Amps
Sample Rate1 MHz Voltage (16666 samples/cycle) 250 kHz current (4166 samples/cycle)
CHANNELSVoltage4 channels
Current4 channels
MEASURED
QUANTITIES
PER CYCLE
RMS VoltageVolts
RMS CurrentAmps
Real PowerWatts
Apparent PowerVAs
Reactive PowerVARs
Phase AngleDegrees
Power FactorWatts/VA
Displacement PFcos (phase angle)
Power UsagekWh, kVARh, kVAh
ACCURACYVoltage0.33% of full scale
Current1.0% of full scale w/o probe
Power1.0% of full scale w/o probe
Phase Angle1.0° w/o probe
Power Factor±0.02 w/o probe
Displacement PF±0.02 w/o probe
POWER FAIL
OPERATION
The recorder can operate without any input voltage for up to 30 minutes. This allows it to record down to 0 volts on all channels during power outages.
HARMONICSVoltageto the 51st
Currentto the 51st
MeasuresMagnitude, phase, THD
COMMUNICATIONSStandardBluetooth®2.0 Wireless, USB 2.0
OptionsMobile Phone, Wi-Fi
INFORMATION
STORAGE
Data Storage16 MB (Standard); 128 MB, 512MBor 1 GB (Optional)
Significant Change1000 records
Flicker 1000 records
RECORD
SETTINGS
Interval Graphs1 cycle to 4 hour interval, user selected, stop-when-full or wrap-around memory modes
Significant Change1V to 8V in 1V steps
Flicker SettingsUser-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141
Waveform CaptureVoltage and current threshold, periodic capture, waveshape, event cross triggers
Transient CapturePeak voltage threshold
POWER SUPPLY REQUIREMENTSVoltage60-600VAC Channel 1 to Common (47-63Hz)
Power Consumption5 Watts max, 15 VA max at 600V
ENVIRONMENTALOperating Temp-20°F to +135°F
HumidityLess than or equal to 85%
Shock60 Hz to 2 kHz, acceleration 25G
Vibration10Hz to 60Hz, amplitude 1.8mm
Max Altitude2.0km (6560 ft), derated above 2.0km
PHYSICAL
DIMENSIONS
Size4.8” L x 3.35” W x 1.84” H
Weightless than 1 lb
CaseNEMA 4X
SAFETYIEC 61010-1, 600V CAT IV, UL listed

Power Monitors, Inc.®

800 N Main St   •   Mt Crawford, Virginia 22841
540.434.4120   •   Toll Free 800.296.4120   •   Fax 540.432.9430