| Base price | $5,295.00 |
| Features | |
| 16 MB | +0.00 |
| 128 MB | +75.00 |
| 512 MB | +125.00 |
| 1 GB | +250.00 |
| Ethernet | +525.00 |
| Cell Modem | +695.00 |
| Transient Capture | +1575.00 |
Overview
Features:
- CAT IV 600 volt rating
- Up to 1 Megahertz voltage sampling
- Up to 5kV transient capture
- Up to 1 GB internal memory
Unrivaled Communication Options:
- USB 2.0
- Ethernet
- Bluetooth® 2.0
- Cell Modem
Description
Reduce fleet and labor costs with this small, rugged, lightweight power quality analyzer. The Revolution is PMI’s state of the art high speed transient power quality monitor with industry leading communications capabilities. The included ProVision software lets you monitor real-time current, flicker, voltage, power factor and more from your desktop, or use a laptop, the PMI Field PC, or a PDA to monitor data from the field.
Benefits:
- 600V CAT IV: For use in a wide range of monitoring environments
- Pocket-size: Can be installed inside meter bases, transformers, and panels
- Bluetooth® 2.0, Cell Phone Modem (optional): Stay safe with wireless data behind closed panel covers
- USB 2.0, built in Ethernet Networking (Optional): For permanent installations
- High sampling rate: Captures high speed transients up to 5000V and 1 MHz.
- UL listed: Increased user safety
- Large memory capacity: Longer monitoring time and very high resolution wave capture.
- NEW Features: E-mail & text alerts, network time sync.
Specs
| INPUTS | AC Voltage | 0 to 600 RMS continuous per phase (±5 kV peak transients) |
| AC Current | 0 to 5000 Amps | |
| Sample Rate | 1 MHz Voltage (16666 samples/cycle) 250 kHz current (4166 samples/cycle) | |
| CHANNELS | Voltage | 4 channels |
| Current | 4 channels | |
| MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps | |
| Real Power | Watts | |
| Apparent Power | VAs | |
| Reactive Power | VARs | |
| Phase Angle | Degrees | |
| Power Factor | Watts/VA | |
| Displacement PF | cos (phase angle) | |
| Power Usage | kWh, kVARh, kVAh | |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale w/o probe | |
| Power | 1.0% of full scale w/o probe | |
| Phase Angle | 1.0° w/o probe | |
| Power Factor | ±0.02 w/o probe | |
| Displacement PF | ±0.02 w/o probe | |
| POWER FAIL OPERATION | The recorder can operate without any input voltage for up to 30 minutes. This allows it to record down to 0 volts on all channels during power outages. | |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st | |
| Measures | Magnitude, phase, THD | |
| COMMUNICATIONS | Standard | Bluetooth®2.0 Wireless, USB 2.0 |
| Options | Mobile Phone, Wi-Fi | |
| INFORMATION STORAGE | Data Storage | 16 MB (Standard); 128 MB, 512MBor 1 GB (Optional) |
| Significant Change | 1000 records | |
| Flicker | 1000 records | |
| RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval, user selected, stop-when-full or wrap-around memory modes |
| Significant Change | 1V to 8V in 1V steps | |
| Flicker Settings | User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141 | |
| Waveform Capture | Voltage and current threshold, periodic capture, waveshape, event cross triggers | |
| Transient Capture | Peak voltage threshold | |
| POWER SUPPLY REQUIREMENTS | Voltage | 60-600VAC Channel 1 to Common (47-63Hz) |
| Power Consumption | 5 Watts max, 15 VA max at 600V | |
| ENVIRONMENTAL | Operating Temp | -20°F to +135°F |
| Humidity | Less than or equal to 85% | |
| Shock | 60 Hz to 2 kHz, acceleration 25G | |
| Vibration | 10Hz to 60Hz, amplitude 1.8mm | |
| Max Altitude | 2.0km (6560 ft), derated above 2.0km | |
| PHYSICAL DIMENSIONS | Size | 4.8” L x 3.35” W x 1.84” H |
| Weight | less than 1 lb | |
| Case | NEMA 4X | |
| SAFETY | IEC 61010-1, 600V CAT IV, UL listed | |