Overview
Kit Contents
Cell Revolution, with transient capture, 128MB memory, and Ethernet
Eagle 120 with Bluetooth and 8MB memory
FCT 4/12 Ultra Slim Four channel 100/1000/5000A flexible 12 in. CTs
FCT 4/24 Ultra Slim Four channel 100/1000/5000A flexible 24 in. CTs
TLAR 4 Four channel 20/200A iron-core CTs
Cell Revolution Antenna Kit
Medium Hard Carrying Case
Description
Save $819 off of the combined list price of $14,214. E-MAIL for details.
Get equipped with the most durable and advanced system available for monitoring real, apparent and reactive power, RMS voltage and current, phase angle, power factor, harmonics and more.
The Revolution Cell Kit combines the advanced remote power quality capabilities of the Revolution with the Eagle 120 receptacle power analyzer. Access the Revolution from anywhere with the embedded cell modem, and use wireless Bluetooth technology to view data remotely from the Eagle 120. The small and medium Ultra Slim Flex CTs allow current measurements in electrical panels, transformers, and switchgear, while the iron-core TLAR clamps are designed for substation or metering CT secondary connections. Kit accessories include an antenna kit to extend the range of the cell Revolution, and a medium hard carrying case.
Specs
| REVOLUTION® | ||
| INPUTS | AC Voltage | 0 to 600 RMS continuous per phase (±5 kV peak transients) |
| AC Current | 0 to 5000 Amps | |
| Sample Rate | 1 MHz Voltage (16666 samples/cycle) 250 kHz current (4166 samples/cycle) | |
| CHANNELS | Voltage | 4 channels |
| Current | 4 channels | |
| MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps | |
| Real Power | Watts | |
| Apparent Power | VAs | |
| Reactive Power | VARs | |
| Phase Angle | Degrees | |
| Power Factor | Watts/VA | |
| Displacement PF | cos (phase angle) | |
| Power Usage | kWh, kVARh, kVAh | |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale w/o probe | |
| Power | 1.0% of full scale w/o probe | |
| Phase Angle | 1.0° w/o probe | |
| Power Factor | ±0.02 w/o probe | |
| Displacement PF | ±0.02 w/o probe | |
| POWER FAIL OPERATION | The recorder can operate without any input voltage for up to 30 minutes. This allows it to record down to 0 volts on all channels during power outages. | |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st | |
| Measures | Magnitude, phase, THD | |
| COMMUNICATIONS | Standard | Bluetooth®2.0 Wireless, USB 2.0 |
| Options | Mobile Phone, Wi-Fi | |
| INFORMATION STORAGE | Data Storage | 16 MB (Standard); 128 MB, 512MBor 1 GB (Optional) |
| Significant Change | 1000 records | |
| Flicker | 1000 records | |
| RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval, user selected, stop-when-full or wrap-around memory modes |
| Significant Change | 1V to 8V in 1V steps | |
| Flicker Settings | User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141 | |
| Waveform Capture | Voltage and current threshold, periodic capture, waveshape, event cross triggers | |
| Transient Capture | Peak voltage threshold | |
| POWER SUPPLY REQUIREMENTS | Voltage | 60-600VAC Channel 1 to Common (47-63Hz) |
| Power Consumption | 5 Watts max, 15 VA max at 600V | |
| ENVIRONMENTAL | Operating Temp | -20°F to +135°F |
| Humidity | Less than or equal to 85% | |
| Shock | 60 Hz to 2 kHz, acceleration 25G | |
| Vibration | 10Hz to 60Hz, amplitude 1.8mm | |
| Max Altitude | 2.0km (6560 ft), derated above 2.0km | |
| PHYSICAL DIMENSIONS | Size | 4.8” L x 3.35” W x 1.84” H |
| Weight | less than 1 lb | |
| Case | NEMA 4X | |
| SAFETY | IEC 61010-1, 600V CAT IV, UL listed | |
| EAGLE® 120 | ||
| INPUTS | AC Voltage | 60 to 140 VAC, 0 to 240 VAC Peak, Neutral-Ground 0-75 VAC RMS |
| AC Current | 0 to 80 Amps RMS (15 Amps continuous) | |
| Sample Rate | 256 samples/cycle/channel | |
| CHANNELS | Voltage | 2 channels |
| Current | 1 channel | |
| MEASURED QUANTITIES PER CYCLE | RMS Voltage | Volts |
| RMS Current | Amps | |
| Real Power | Watts | |
| Apparent Power | VAs | |
| Reactive Power | VARs | |
| Phase Angle | Degrees | |
| Power Factor | Watts/VA | |
| Displacement PF | cos (phase angle) | |
| Power Usage | kWh, kVARh, kVAh | |
| COMMUNICATIONS | Type | USB, Bluetooth®Wireless (optional) |
| INFORMATION STORAGE | Interval Graphs | 1.2 MB (Standard) 6.9 MB (with memory option) |
| Significant Change | 1000 records | |
| Flicker | 1000 records | |
| Waveform Capture | 256 KB (standard) 1.7 MB (with memory option) | |
| RECORD SETTINGS | Interval Graphs | 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes |
| Significant Change | 1V to 8V in 1V steps | |
| Flicker | User-defined, or conform to IEEE1453/IEC61000-4-15,and IEEE Std. 141 | |
| Waveform Capture | Voltage and current threshold, periodic capture | |
| ENVIRONMENTAL | Operating Temp | -20°F to +135°F |
| Shock | 60 Hz to 2 kHz, acceleration 25G | |
| Vibration | 10Hz to 60Hz, amplitude 1.8mm | |
| ACCURACY | Voltage | 0.33% of full scale |
| Current | 1.0% of full scale | |
| Power | 1.0% of full scale | |
| Phase Angle | 1.0° | |
| Power Factor | ±0.02 | |
| Displacement PF | ±0.02 | |
| PHYSICAL DIMENSIONS | Size | 4.9” L x 2.7” W x 1.25” H |
| Weight | 0.5 lbs | |
| HARMONICS | Voltage | to the 51st |
| Current | to the 51st | |
| Measures | magnitude, phase, THD | |
| ULTRA SLIM FLEX CTs | ||||
| ELECTRICAL SPECIFICATIONS | Switchable Ranges | 1 to 100A, 1 to 1000A, 1 to 5000A | ||
| Operating Limit | 1 to 5000A | |||
| Controls | Range is chosen from the recorder, PC, or PDA software. | |||
| Power Source | Power is supplied by connection to PMI recorder. No external battery or other power source is required. | |||
| Linearity | ±0.05% | |||
| Phase Shift | ≤±0.5% at 50 to 60 Hz | |||
| Frequency Range | 8Hz to 10kHz | |||
| Crest Factor (mid range) | 100A and 1000A scale: 3.0 5000A scale: 1.6 | |||
| Position Sensitivity | ±1.5% 1 in from connector | |||
| WORKING VOLTAGE | Sensor | 600V AC to earth | ||
| Module | 600V AC to earth | |||
| ACCURACY | ± 1% of full scale | |||
| SAFETY | Double Insulated | |||
| Sensor | 600V CAT IV | |||
| Module | 600V CAT III | |||
| Pollution Degree 2 | ||||
| PMI RECORDER CAPABILITY | iVS-3/600E may require a firmware upgrade | |||
| ELECTRICAL SPECIFICATIONS | Switchable Ranges | 1 to 100A, 1 to 1000A, 1 to 5000A | ||
| Operating Limit | 1 to 5000A | |||
| Controls | Range is chosen from the recorder, PC, or PDA software. | |||
| Power Source | Power is supplied by connection to PMI recorder. No external battery or other power source is required. | |||
| Linearity | ±0.05% | |||
| Phase Shift | ≤±0.5% at 50 to 60 Hz | |||
| Frequency Range | 8Hz to 10kHz | |||
| Crest Factor (mid range) | 100A and 1000A scale: 3.0 5000A scale: 1.6 | |||
| Position Sensitivity | ±1.5% 1 in from connector | |||
| WORKING VOLTAGE | Sensor | 600V AC to earth | ||
| Module | 600V AC to earth | |||
| ACCURACY | ± 1% of full scale | |||
| SAFETY | Double Insulated | |||
| Sensor | 600V CAT IV | |||
| Module | 600V CAT III | |||
| Pollution Degree 2 | ||||
| PMI RECORDER CAPABILITY | iVS-3/600E may require a firmware upgrade | |||
| MECHANICAL MATERIALS | Sensor Jacket | Polyurethane UL94V0 | ||
| Connector | FR Polypropylene UL94V0 | |||
| Cable Jacket | Polyurethane UL94V0 | |||
| PHYSICAL DIMENSIONS | Min. Bending Radius | 1 in (25.4 mm) | ||
| Sensor Diameter | .310 in (7.9 mm) | |||
| Connector Diameter | 1.07 in max (27.2 mm) | |||
| Sensor Output Cable Length | 48 in (1.2 m) | |||
| ENVIRONMENTAL | Operating Temperature | -20 to 135°F (-29 to 57°C) | ||
| Altitude Operating | 0 to 2000m, derated above 2000m | |||
| Case Protection | Sensor and Module IP65 per IEC 529 | |||
| PMI CT MODEL NUMBER | .../12 | .../24 | .../36 | .../48 |
| LENGTH (OPEN) | 12 in. 305 mm | 24 in. 610 mm | 36 in. 915 mm | 48 in. 1220 mm |
| O.D. (CLOSED) | 4.15 in. 105 mm | 8.3 in. 210 mm | 12 in. 305 mm | 15.9 in. 404 mm |
| I.D. (CLOSED) | 3.5 in. 89 mm | 7 in. 178 mm | 10.9 in. 277 mm | 14.7 in. 372 mm |
| TLARs | ||
| ELECTRICAL SPECIFICATIONS | Current Ranges | 20A, 200A AC |
| Operating Limit | 200A Continuous | |
| Frequency Range | 40 to 10kHz | |
| Working Voltage | 600 VAC max | |
| Influence of conductor position in jaw | 0.5% of reading at 50/60Hz | |
| Influence of adjacent conductor | 1.50% | |
| Influence of frequency | 40Hz to 1kHz: 3% of reading, 1kHz to 10kHz: 12% of reading | |
| PHASE SHIFT | 1-20A | ≤3 degrees |
| 20-80A | ≤2 degrees | |
| 80-200A | ≤2.5 degrees | |
| ACCURACY | 20A scale | 1 to 20 A: 1.5% of reading ±0.1A |
| 200A scale | 1.5% of reading ±0.5A | |
| SAFETY | Rating | UL 61010B-1 |
| IEC 61010-1 | ||
| 600V CAT III | ||
| PMI RECORDER CAPABILITY | 10A range only with iVS-3/600E and ViPs with SNs lower than 61000, otherwise adjustable 20A/200A range | |
| ENVIRONMENTAL | Operating Temp | 14 to 131°F -10 to 55°C |
| Operating Relative Humidity | 10-35°C 85% RH | |
| Case Protection | Probes - IP40, Enclosure - IP65 | |
| PHYSICAL DIMENSIONS | Maximum Conductor Size | 0.78 in (20 mm), bus bar 20 x 5 mm |
| Probes | 5.47 x 2.00 x 1.18 in (139 x 51 x 30 mm) | |
| Enclosure | 2.36 x 1.38 x 0.67 in | |
| Weight | TLAR+200/3 - 0.75 lb TLAR+200/4 - 1.00 lb | |
| Probe Leads | 4 ft, 600V rating | |
| Output Cable | 9 in, 600V rating | |